Running watts vs. starting watts, explained
This is the single concept that determines whether you buy the right generator. Get it wrong and a generator that looks big enough on paper will stall the moment your refrigerator's compressor kicks on.
Running watts: the steady draw
Running watts (also called rated or continuous watts) is the power an appliance draws while operating normally. A 1,500 W space heater draws 1,500 watts the entire time it's on. A modern refrigerator draws roughly 150–400 watts while the compressor runs. Simple.
Starting watts: the surge nobody budgets for
Starting watts (surge or peak watts) is the brief burst of extra power — lasting a few seconds — that electric motors and compressors need to get moving from a dead stop. The multiplier is typically 2 to 3 times the running watts:
- Refrigerator: ~250 W running → ~1,200 W starting
- Well pump (1/2 HP): ~1,000 W running → ~2,100 W starting
- Window AC (10,000 BTU): ~1,500 W running → ~3,500 W starting
- Furnace blower (1/2 HP): ~875 W running → ~2,350 W starting
Resistive loads — heaters, toasters, incandescent lights, kettles — have no surge. What they draw is what they draw. Electronics like TVs and laptops also have no meaningful surge.
The formula pros use
You don't need to budget surge for every motor at once — motors rarely all start in the same second. The standard method used in manufacturer sizing worksheets:
Generator peak watts needed = (sum of all running watts) + (largest single motor's additional starting watts)
Where "additional starting watts" = starting watts minus running watts for that one motor. Then add headroom: plan to load a generator to about 80% of its running rating continuously, not 100%.
Our calculator does exactly this math, with 25% headroom on running watts and a 10% margin on the peak.
The marketing trap: peak vs. running ratings
Portable generators are advertised by their peak watts — the number they can sustain for seconds. The running watts rating, usually about 80% of peak, is the number that actually powers your house. A "7,500 W" portable typically delivers ~6,000 running watts. Always size by the running rating and treat peak as your surge budget.
Quick reference
- Motors and compressors: budget 2–3x running watts for starting.
- Heating elements and lights: starting = running.
- Size for the largest single motor start, on top of everything already running.
- Buy by running watts; keep 20–25% headroom.
- When in doubt, check the appliance nameplate — our calculator lets you override every value.
Worked example: a furnace, a fridge, and one honest total
Take a typical winter outage list, using the figures from this page. A refrigerator (250 W running, 1,200 W starting), a furnace blower (875 W running, 2,350 W starting), LED lighting (100 W, no surge), and a TV with a router (150 W, no surge).
- Running total: 250 + 875 + 100 + 150 = 1,375 W
- Largest extra surge: the blower, 2,350 minus 875 = 1,475 W on top of its running draw
- Peak the generator must survive: 1,375 + 1,475 = 2,850 W, for the few seconds the blower starts
- Continuous load check: 1,375 W is about half the running rating of a typical 3,500 W unit (about 2,800 running watts), a comfortable load for hours
Now add a window air conditioner (1,500 W running, 3,500 W starting). Running climbs to 2,875 W, and if the AC starts while the blower runs, the peak becomes 2,875 + 2,000 = 4,875 W, beyond that same generator. The fix is not always a bigger unit: run the AC and the furnace one at a time, and the smaller generator stays in the game.
Size a generator in five steps
- List what runs at the same time. Not everything you own, just the loads that genuinely overlap during your outage, camping trip, or workday.
- Write down running watts for each. Nameplates beat memory. Our calculator preloads typical values, but your appliance's label is the authority.
- Find the largest motor on the list and note its extra starting watts, the gap between its starting and running figures.
- Add: total running watts plus that one extra surge. That sum is your peak requirement.
- Choose a unit whose running rating covers your total at about 80% load and whose peak clears your peak requirement. If either fails, step up one size.
Common surge mistakes
- Adding every motor's surge at once. That oversizes the generator, sometimes by a full class. Motors almost never start in the same second.
- Trusting the big number on the box. The advertised figure is peak watts. The running rating, roughly 80% of it, is what powers your house hour after hour.
- Forgetting the well pump or sump pump. They start on their own schedule, mid-outage, usually at the worst moment. If they are on your must-run list, their surge belongs in the math.
- Running at 100% load for hours. A generator loaded to its ceiling runs hot, loud, and thirsty. Headroom is how the unit survives a long outage.
- Feeding motors through a long, thin extension cord. Voltage drop makes motors start harder and run hotter. Use short, heavy-gauge cords for compressors.