Running watts vs. starting watts, explained

This is the single concept that determines whether you buy the right generator. Get it wrong and a generator that looks big enough on paper will stall the moment your refrigerator's compressor kicks on.

Running watts: the steady draw

Running watts (also called rated or continuous watts) is the power an appliance draws while operating normally. A 1,500 W space heater draws 1,500 watts the entire time it's on. A modern refrigerator draws roughly 150–400 watts while the compressor runs. Simple.

Starting watts: the surge nobody budgets for

Starting watts (surge or peak watts) is the brief burst of extra power — lasting a few seconds — that electric motors and compressors need to get moving from a dead stop. The multiplier is typically 2 to 3 times the running watts:

Resistive loads — heaters, toasters, incandescent lights, kettles — have no surge. What they draw is what they draw. Electronics like TVs and laptops also have no meaningful surge.

The formula pros use

You don't need to budget surge for every motor at once — motors rarely all start in the same second. The standard method used in manufacturer sizing worksheets:

Generator peak watts needed = (sum of all running watts) + (largest single motor's additional starting watts)

Where "additional starting watts" = starting watts minus running watts for that one motor. Then add headroom: plan to load a generator to about 80% of its running rating continuously, not 100%.

Our calculator does exactly this math, with 25% headroom on running watts and a 10% margin on the peak.

The marketing trap: peak vs. running ratings

Portable generators are advertised by their peak watts — the number they can sustain for seconds. The running watts rating, usually about 80% of peak, is the number that actually powers your house. A "7,500 W" portable typically delivers ~6,000 running watts. Always size by the running rating and treat peak as your surge budget.

Quick reference

Worked example: a furnace, a fridge, and one honest total

Take a typical winter outage list, using the figures from this page. A refrigerator (250 W running, 1,200 W starting), a furnace blower (875 W running, 2,350 W starting), LED lighting (100 W, no surge), and a TV with a router (150 W, no surge).

Now add a window air conditioner (1,500 W running, 3,500 W starting). Running climbs to 2,875 W, and if the AC starts while the blower runs, the peak becomes 2,875 + 2,000 = 4,875 W, beyond that same generator. The fix is not always a bigger unit: run the AC and the furnace one at a time, and the smaller generator stays in the game.

Size a generator in five steps

  1. List what runs at the same time. Not everything you own, just the loads that genuinely overlap during your outage, camping trip, or workday.
  2. Write down running watts for each. Nameplates beat memory. Our calculator preloads typical values, but your appliance's label is the authority.
  3. Find the largest motor on the list and note its extra starting watts, the gap between its starting and running figures.
  4. Add: total running watts plus that one extra surge. That sum is your peak requirement.
  5. Choose a unit whose running rating covers your total at about 80% load and whose peak clears your peak requirement. If either fails, step up one size.

Common surge mistakes

Related guides

Inverter vs. conventional generators

Which type fits your use case — and what "clean power" actually means.

What size for home, camping, or jobsite?

Typical wattage ranges with example load lists.